Three-phase hybrid inverter | 8–12kW output | 20A high-current PV string compatibility | 100% unbalanced load capability | 1.1x sustained AC overload | Parallel ready. Diesel generator integration for seamless grid/gen transfer. Comprehensive protection: PV reverse polarity, AC/DC surge, insulation monitoring, RCD. IP65 | Forced air cooling | -25℃~60℃ operation | 240A charge/discharge | CAN/RS485 & optional 4.3" display. The ideal choice for high-end residential storage systems demanding efficiency, flexibility, and intelligence.
Contact Us立即咨询
service hotline: +86 13612871478
Parameter Category Item R8KL3 R10KL3 R12KL3
PV Input Max. Power (kW) 12 15 18
Startup Voltage (V) 200 200 200
Max. PV Voltage (V) 1,000 1,000 1,000
MPPT Voltage Range (V) 200~850 200~850 200~850
Rated Voltage (V) 600 600 600
Number of MPPT Trackers 2 2 2
PV Strings per MPPT 1/1 1/1 1/1
Max. Input Current per MPPT (A) 20/20 20/20 20/20
Max. Short Circuit Current per MPPT (A) 30/50 30/50 30/50
Battery Parameters Battery Voltage Range (V) 40~60 40~60 40~60
Max. Charge Voltage (V) 60 60 60
Max. Charge Current (A) 160 200 240
Max. Discharge Current (A) 160 200 240
Communication Interface CAN / RS485 CAN / RS485 CAN / RS485
AC Output (Grid-Tied) Rated Output Power (kW) 8 10 12
Rated Output Current (A) 11.6 14.5 17.5
Rated Grid Voltage (V) 220/380; 230/400 220/380; 230/400 220/380; 230/400
Grid Voltage Range (V) 340~440 340~440 340~440
Rated Grid Frequency (Hz) 50/60 50/60 50/60
Grid Frequency Range (Hz) 45~55 / 55~65 45~55 / 55~65 45~55 / 55~65
THDi <3% <3% <3%
Grid Type 3W+N+PE 3W+N+PE 3W+N+PE
AC Output (Off-Grid) Rated Output Power (kW) 8 10 12
Max. AC Input/Output (kVA) 8.8 11 13.2
Rated Output Voltage (V) 220/380; 230/400 220/380; 230/400 220/380; 230/400
Rated Output Current (A) 11.6 14.5 17.5
Max. Input/Output Current (A) 11.6/12.8 14.5/16 17.5/19.2
Rated Output Frequency (Hz) 50/60 50/60 50/60
Peak Output Power 2x Power for 10s 2x Power for 10s 2x Power for 10s
Transfer Time (ms) Up to 10ms Up to 10ms Up to 10ms
THDu <3% (Linear Load) <3% (Linear Load) <3% (Linear Load)
Max. Continuous Bypass Current (A) 50 50 50
Overload Capability Supports 100% Unbalanced Output, Max. Output per Phase: 50% of Rated Power Same as left Same as left
Efficiency Max. Efficiency 97.6% 97.6% 97.6%
European Efficiency 97.0% 97.0% 97.0%
MPPT Efficiency >99% >99% >99%
Protection PV Reverse Polarity Protection Yes Yes Yes
PV DC Switch Yes Yes Yes
DC Surge Protection DC Type II DC Type II DC Type II
AC Surge Protection AC Type III AC Type III AC Type III
Insulation Resistance Detection Yes Yes Yes
RCD Detection Yes Yes Yes
AC Output Short Circuit Protection Yes Yes Yes
Grid Monitoring Yes Yes Yes
Lightning Protection Yes Yes Yes
Arc Fault Detection Optional Optional Optional
General Parameters Dimensions W×D×H (mm) 420×262×650 420×262×650 420×262×650
Weight (kg) <40 <40 <40
Ingress Protection IP65 IP65 IP65
Noise (dB) <55 <55 <55
Operating Temperature Range (°C) -25~+60 (Derating >45) -25~+60 (Derating >45) -25~+60 (Derating >45)
Cooling Forced Air Cooling Forced Air Cooling Forced Air Cooling
Operating Altitude (m) 3,000 (Derating >2,000) 3,000 (Derating >2,000) 3,000 (Derating >2,000)
Inverter Topology Non-Isolated Non-Isolated Non-Isolated
Communication RS485 / Wi-Fi / GPRS / CAN RS485 / Wi-Fi / GPRS / CAN RS485 / Wi-Fi / GPRS / CAN
Display 4.3" (Optional) 4.3" (Optional) 4.3" (Optional)